Some amends and supplements of the

Circular No. 05/2025/TT-BCT⚠️ - New regulations on technical requirements for power transmission and distribution systems

within:
  • Circular No. 46/2025/TT-BCT - Amendments to the responsibility for payment of expenses and the regime of reporting on the reduction or cessation of electricity supply
  • Effected from: 22-Sep-2025
    New additions
    Circular 46/2025/TT-BCT has new additions compared to Circular 05/2025/TT-BCT as follows:
    • Article 1.2: Clause 13 Article 3 is added: The definition of "provincial-level People's Committee" is added to clarify the subjects of application and avoid different interpretations of this term.
    • Article 2.2: Supplementing Clause 8, Article 27: Vietnam Electricity is responsible for formulating and promulgating guidelines on the scope, layout and technical requirements for protective relay equipment for generating units, transformers, busbars, compensators and lines connected to the distribution power grid, collect opinions of distribution dispatching units and relevant units, report to the Ministry of Industry and Trade before applying.
    • Article 2.6: Clause 9 of Article 43 is added: Investors of solar power systems with a capacity of 100 kW or more and choose to sell excess electricity into the national power system shall be responsible for negotiating and reaching agreement with power distribution units on equipment and means connected to the collection system, supervision and control of the distribution dispatching level. In case of not selling excess electricity to the national power system, the investor of a solar power system with a capacity of 100 kW or more shall be responsible for negotiating and reaching agreement with the power distribution unit on equipment and means connected to the collection and supervision system of the distribution dispatching level
    Changes
    Below is a summary of the changes between Circular 05/2025/TT-BCT and Circular 46/2025/TT-BCT:
    SpotlightOldNew
    Definition of Power Distribution Unit (1.1)Electricity distribution unit means an electricity unit licensed to operate electricity.Electricity distribution units include the Electricity Corporation under EVN and the Provincial Electricity Company.
    Payment of power interruption costs (1.3, 1.4)There is no clear regulation on the costs involved.It stipulates that the requesting party to stop the electricity supply, or the violating buyer must pay the cost to the electricity seller.
    Power Supply Interruption Report (1.5, 1.6, 1.7)Units report directly to the Ministry of Industry and Trade.Units report to the provincial People's Committee.
    VNU's evaluation indicators (2.1)Organization of formulation and promulgation of relay scope, layout and technical requirementsOrganize the formulation and promulgation of guidelines on the scope, layout and technical requirements of relays
    SCADA Connection Requirements for Power Plant (2.3)Grid-connected power plant that has not yet connected the Control Center must be equipped with a Gateway or RTU and establish two physically independent connections to the SCADA system of the Dispatching Level with Control AuthorityPower plant connected to the transmission grid that is not connected Control Center must be equipped with a Gateway or RTU and establish two physically independent connections to the SCADA system of the Dispatching Level with Control Authority
    SCADA Connection Requirements for Power Plant (2.3)The power plant connected to the Control Center must be equipped with a Gateway or RTU that is established, one connection to the SCADA system of the Dispatching Level with control authority and two connections to the control system at the Control CenterThe power plant connected to the transmission grid connected to the Control Center must be equipped with a Gateway or RTU that is established, one connection to the SCADA system of the dispatching level with control authority and two connections to the control system at the Control Center
    Wind and solar power plant capacity control (2.4)Requirements for power plants with a capacity of over 30MW to be equipped with AGC systemsRegulations on power plants with a total capacity of 10MW to 30MW and connected to a voltage level of 110 kV or more
    Power purchase agreement documents in the dossier (2.8)Signed Power Purchase Agreement or Agreement on Power PurchaseSigned power purchase contracts or agreements on electricity purchase, sale, delivery and receipt, except for power plants affiliated to the Electricity of Vietnam in the period of not participating in the competitive electricity market
    Equipment TestingNo Specific RequirementsRequires SCADA, FRS/PQ/PMU connection tests to be performed prior to the time of energizing in accordance with the range
    Post-Energized Equipment Test(2.10)Request information only when the device respondsRequires the completion of tests within a period of no more than 1 year, even if the primary source is not available
    Power plant system retesting (2.17)No clear requirements for responsibilities and specificationsSupplementing the responsibilities of the dispatching level in confirming test results
    Abolition of contracted requirements, old equipmentApplicable to all buildingsConditional application of procurement contracts, signed before the effective date of the Circular
    Tests and TestsNo AGC Tests RequiredAGC Connection Test Supplement
    Repeal or Expiration
    Circular 46/2025/TT-BCT has annulled or invalidated a number of provisions from previous legal documents, specifically:
    • Article 5.1: Clauses 2 and 7, Article 42 of Circular No. 05/2025/TT-BCT are annulled.
    • Article 5.2: Clause 7, Article 161 of Circular No. 05/2025/TT-BCT is annulled.
    • Article 5.3: Clause 10 Article 26, Clause 1 Article 41, Clause 1 Article 70, Clause 4 Article 100, Clause 3 Article 136, Clause 3 Article 137, Clause 5 Article 221 of Circular No. 06/2025/TT-BCT are annulled.
    • Article 5.4: Articles 13, 18, 22, 27, 78, 128, 240, 241, 242 of Circular No. 06/2025/TT-BCT are annulled.
    Overview of the effects of differences
    • Clearer about responsibilities and processes: The amendments and supplements help to clarify the responsibilities of each unit (Dispatching Unit, Transmission, Distribution, Power Generation, Customer), minimizing possible disputes during the implementation process.
    • Enhancing flexibility and adaptability: Allowing the parties to agree in some cases (e.g. backup metering location, metering method) helps to increase flexibility, in accordance with the actual conditions of each project and each area.
    • Prioritizing safety and reliability: The modifications to testing, equipment inspection, maintenance, and operation coordination are all aimed at ensuring safety, stability and reliability for the national power system.
    • Adjustment of reporting information and data: Adjustment of reporting data, helping the management and supervision of the authorities to be stricter and more effective.
    • Promoting the development of renewable energy: Adjustments and additions related to wind and solar power plants, BESS show interest in integrating renewable energy sources into the power system in a safe and efficient way.
    • Strengthening the role of dispatching levels: Reflected in the adjustment of roles and responsibilities for both the national dispatching level and the local dispatching level.
    Posted date: 17-Sep-2025 17 2025 4:42PM VN
    Some new points of the:

    Circular No. 05/2025/TT-BCT⚠️ - New regulations on technical requirements for power transmission and distribution systems

    on replacing of:
    • Circular No. 39/2022/TT-BCT⛔ - Amendments to regulations on power plants
    Effective date: 01-Feb-2025
    What's new
    The following regulations are completely new, only in Circular 05/2025/TT-BCT and do not appear in the replaced documents:
    Impact reliability of the protection relay system (Article 26.7*): The impact reliability of the protection relay system is not less than 99%.
    Equipped with a phase angle measuring device (PMU) (Article 26.8.c*): A power plant with a total installed capacity of 300 MW or more must be equipped with a device with a phase angle measurement (PMU) function.
    Communication transmission time for line protection relays (Article 26.8.e and Article 27.7.a*): Power transmission lines with a voltage of 220 kV or more connected to generating units or distribution yards of power plants must have 02 independent communication channels serving the transmission of protection relay signals between two ends of the line with a transfer time not greater than 20 ms.
    Damping ratio (Article 37.8*): Generating units of power plants with a capacity of over 30 MW must be equipped with Power System Stabilisers (PSS) capable of degrading fluctuations with frequencies in the range from 0.1 Hz to 5 Hz, contributing to improving the stability of the power system. The generating unit must install and calibrate the parameters of the PSS equipment to ensure that the PSS equipment has a damping ratio of not less than 5%.
    • Requirements for Storage Battery Systems (Article 44). This is a completely new item due to the specific regulations on the specifications and operational requirements of the BESS energy storage battery system connected to the grid.
    • Record of inspection of conditions for electrification of connection points (Article 50, Article 58) requires a record of acceptance with signatures certifying eligibility for electrification of connection points to continue the steps of electrification and commissioning.
    Explanations of terms related to power metering (Article 3*): Terms such as "Current Variable (CT)", "Voltage Variable (VT)", "Metering Database", "Metering Meter", "Metering System Investment Unit",... are defined more clearly and in detail.
    Requirements for password layers and security of metering information (Article 99*): Specific regulations on the classification of meter passwords (Setting password, Time Sync password, Read-Only password) and management and security responsibilities for each type of password.
    Changes
    The following table summarizes the main changes between Circular 05/2025/TT-BCT and the replaced documents:
    SpotlightOldNew
    Definition of Solar Power Plant Rated CapacityThere is no clear definition yet.The maximum alternating current power capacity of the plant is calculated and announced, in accordance with the DC power capacity of the solar power plant according to the plan (Article 3.6).
    Frequency ControlFrequency control in the power system (hereinafter abbreviated as frequency control) is the control process in the power system to maintain the stable operation of the system, including primary frequency control and secondary frequency control.The process of controlling the frequency of level 3 (Article 3.14.c) is added to bring the frequency of the power system to operate stably according to current regulations and ensure the economic allocation of generating capacity for generating units.
    Inverse Order Component of Phase VoltageThe inverse order component of the phase voltage must not exceed 3% of the nominal voltage for the nominal voltage levels in the transmission power grid.The inverse order component of the phase voltage must not exceed 03% of the nominal voltage for high-voltage and ultra-high-voltage levels, or 05% of the nominal voltage for medium-voltage and low-voltage voltage levels (Article 7.1).
    Frequency range to maintain the operation of wind and solar power plantsThere is no specific maintenance time for each frequency band.Stipulating the minimum time of maintaining the operation of power generation of wind power plants and solar power plants corresponding to the frequency bands of the power system (Article 40.2, Article 41.2).
    Relative slope of a static linear lineThere is no regulation on the relative slope of a static lineWind power plants and solar power plants are capable of reducing their effective capacity according to the relative slope of the droop characteristics in the range from 02% to 10% (Article 40.3, Article 41.3)
    Reactive voltage and power control modeNo regulation on voltage control mode and reactive powerWind power plants and solar power plants are capable of controlling voltage and reactive power according to the following modes: Voltage control mode according to voltage set values, voltage control mode according to voltage regulation slope characteristics (voltage/reactive power relationship characteristics), control mode according to the reactive power setting, control mode according to power factor (Article 40.5, Article 41.5).
    Maintain power generation operation corresponding to the voltage rangeThere is no regulation on thresholds and maintenance times for each voltage range.Wind power plants and solar power plants at all times that are connected to the grid must be able to maintain power generation operations corresponding to the voltage range at the high-voltage side of the booster transformer of the power plant during the period (Article 40.6, Article 41.6).
    Removal points
    Circular 05/2025/TT-BCT has removed a number of regulations compared to the replaced documents, specifically:
    • The contents of connection for selling electricity to customers connecting to medium voltage or lower in Circular 39/2015/TT-BCT: Circular 05/2025/TT-BCT does not have separate regulations on the order, procedures and technical requirements for the connection to customers using low-voltage and medium-voltage electricity as prescribed in Circular 39/2015/TT-BCT fix. This can be understood to mean that this type of connection will be in accordance with general regulations or there will be other documents regulating it.
    • Abolition of the responsibility to report to the Electricity Regulatory Authority on each type of incident and impact. In previous Circulars, the responsibility to report to the Electricity Regulatory Authority is very specific about types of incidents.
    • Detailed procedures for testing and test supervision: Circular 05/2025/TT-BCT only stipulates general requirements for equipment testing without going into detailed procedures.
    Important Note: This is an analysis based on the information provided. For the most accurate and complete information, please refer directly to Circular 05/2025/TT-BCT and the replaced documents.